A linear motor drive is not a rotary servo drive with different firmware. It has to do two things a rotary drive never has to do, and both of them happen before the axis has moved a millimetre.
It has to work out where the forcer sits relative to the magnet poles, because unlike a rotary servo there is no factory-set relationship between the encoder and the magnetic field. And it has to close its loop around a scale that is not attached to the motor at all, mounted somewhere on the machine, with its own resolution, its own signal format and its own limits.
Those two requirements shape everything else — the part number, the wiring, the commissioning sequence and most of the fault codes you will ever see on the display. TechMan Robotics supplies linear motor axes with Adtech, Panasonic and Servotronix drives, and this page covers how the drive is chosen and what the choice commits you to.
Commutation: Three Ways the Linear Motor Drive Finds the Poles
Get this wrong and the axis either refuses to enable or runs away. There are three routes, and the machine decides which one is available.
Hall signals from the motor. The forcer carries Hall elements that report coarse pole position directly. On the Adtech QXL series this is the EN2 port, wired straight to the motor’s Hall elements, supplying them 5 V and reading single-ended U, V and W signals. Worth knowing before you order: only the H-version QXL drives carry this function. On Panasonic drives the equivalent is the X6 connector, carrying CS1, CS2 and CS3 inputs.
Automatic pole estimation. The drive injects current, watches how the mover responds and infers the pole relationship without any Hall signal. Panasonic’s A6L series handles axes both with and without a pole position signal, detecting the relationship automatically, and its setup routine also sets sensor direction and gains.
Estimation is convenient and it has a hard boundary. It needs some travel and some time to run, so a mover pinned against a hard stop cannot complete it. It also fails where a constant load pulls the mover during the routine — Panasonic states plainly that pole position estimation should not be used on vertical axes with load offset or high friction. A vertical linear motor axis therefore needs Hall signals or an absolute scale, and this has to be settled at the design stage rather than discovered at commissioning.
An absolute scale. The scale reports true position at power-up, so nothing has to be estimated and nothing has to move.
The difference shows up every single power cycle. With an incremental scale and Hall feedback on a Servotronix CDHD, a phase-finding step runs at every power-up. If the machine has the mover sitting under a dispensing head or inside a fixture, that movement is a design problem, not an inconvenience.
Linear Motor Drive Is the Second Speed Ceiling
The scale has a speed limit set by its signal period and reading head frequency. The drive has a separate one, set by how fast its feedback input can count.
Panasonic’s X5 feedback connector accepts A, B and Z pulses at up to 4 Mpulse/s after quadrature. Convert that into axis speed and the resolution you chose becomes a speed specification:
| Scale resolution |
Speed limit at 4 Mpulse/s |
|
1 μm |
4 m/s |
| 0.5 μm |
2 m/s |
| 0.1 μm |
0.4 m/s |
The axis runs at the lower of the two ceilings — the scale’s and the drive’s. Both have to be checked against the motion profile, and a resolution that looked harmless on the scale datasheet can be capped again here.
What does not bind is the inverter’s output frequency, which is the number people tend to worry about. The Adtech QXLH02NT01-B nameplate gives a maximum output frequency of 1200 Hz. Electrical frequency on a linear motor is velocity divided by the magnetic pole pitch, and the UMA series runs 30 mm on UMA22 through to 84 mm on UMA50. At 1200 Hz that works out to roughly 36 m/s on the smallest frame and 100 m/s on the largest — orders of magnitude beyond anything the mechanics will do. The count rate binds long before the inverter does.
Size the Linear Motor Drive on Peak Current
A linear motor’s peak current runs four to five and a half times its continuous rating. Servo drives are quoted with a much narrower ratio, typically two to four. The two do not line up, and sizing on continuous current alone lands you short every time.
Take UMA22-61-19 in series winding: 1.6 Arms continuous, 8 Arms peak. Sized on the continuous figure you would reach for the smallest 200 V drive in the Panasonic range at 1.1 Arms rated. Its peak is 3.9 Arms. So is the next one up at 1.5/4.9, and the one after that at 2.4/7.4. The first unit that covers 8 Arms of peak is rated 4.1 Arms continuous — three sizes above what the continuous figure suggested, for a motor producing 19 N.
Take UMA50-673-934: 6 Arms continuous, 36 Arms peak. The drive that covers it is rated 12.5 Arms continuous with 37.5 Arms peak.
Then check the second half of the question, which is duration. Peak current ratings assume a limited window. Confirm the drive can hold its peak for as long as your acceleration ramp actually lasts, rather than for whatever nominal period appears in the datasheet.
The Feedback Interface Is Fixed in the Part Number
On the Adtech series the encoder format is the second-to-last field of the model code. T01 is digital A/B/Z. T02 is BiSS-C and EnDat. That decision is made when the drive is ordered, and it cannot be changed afterwards in software.
There is a specific consequence worth knowing if you were planning on an analogue scale. A 1 Vpp sine-cosine output gives fine resolution without the speed penalty that digital high-resolution heads carry, which makes it attractive on a fast axis. The Adtech EN1 port does accept 1 Vpp — through an external interpolator, part number QX-XEN01, which converts the analogue signal to BiSS before the drive sees it. That is an extra component, an extra enclosure position and an extra set of connections, and it needs to be in the bill of materials from the start.
The Servotronix CDHD takes a different approach, putting several feedback types onto one 26-way C4 connector. Pins 1, 2, 14 and 15 are dual-function: incremental A and B differential pairs, or SSI data and clock, depending on what is configured in the ServoStudio motor setup and feedback windows. Wire for one and configure for the other and the axis will not run, with nothing obviously wrong at the connector. Two more details on that connector catch people out — Hall inputs must be single-ended, and pins 12 and 25 for the motor temperature sensor must be left unconnected if the motor does not have one.
Scale types, resolutions and the mounting side of this decision are covered on the linear motor feedback system page.
Linear Motor Drive Platforms
Adtech QXL series

Purpose-built for linear motors, with the motor type declared in the model code. Reading QXLH02NT01-B:
| Field | Meaning |
| QX | Model series |
| L | Suitable motor type — linear motor |
| H | Drive version: P universal, H high level, C customised |
| 02 | Continuous output current: 02 = 2 A, then 04, 05, 06, 10, 15 A |
| N | Input voltage: N = 220 VAC, T = 380 VAC (in development) |
| T01 | Encoder type: T01 digital ABZ, T02 BiSS-C and EnDat |
| -B | B type and BPro type drive |
The nameplate for that model gives single or three phase input at 200–300 V, 50/60 Hz, against three phase output at 0–326 V and up to 1200 Hz. Communications run over CN2 and CN3, carrying RS232 for the tuning software and RS485 for MODBUS multi-drop across several drives.
Panasonic MINAS A6L series
Covers ironless, iron-core, shaft-type and linear motors on one platform, accepting serial-communication incremental and absolute sensors as well as A/B/Z, with or without a pole position signal. Its automatic setup routine establishes pole position, sensor direction and gains.
| Supply | Rated current (Arms) | Maximum current (Arms) |
| Single phase 100 V | 1.1 / 1.6 / 2.5 / 4.6 | 3.7 / 5.6 / 7.5 / 14.4 |
| Single or three phase 200 V | 1.1 / 1.5 / 2.4 / 4.1 / 5.9 / 9.3 | 3.9 / 4.9 / 7.4 / 13.3 / 17.1 / 26.2 |
| Three phase 200 V | 12.5 / 19.3 / 27.1 | 37.5 / 56.6 / 72.1 |
Interface variants cover pulse-train, multi-function, RTEX and EtherCAT in standard and multi-function forms.

Image 1. Panasonic MINAS A6L servo drive
Servotronix CDHD series
Reading CDHD-006-2A-AP-1: rating 006, supply configuration 2A, interface AP, analogue input option 1.
| Supply |
Continuous / peak current (Arms) |
| 120 / 240 VAC | 1.5/4.5 · 3/9 · 4.5/18 · 6/18 · 8/28 · 10/28 · 13/28 · 20/48 · 24/48 |
| 400 / 480 VAC | 3/9 · 6/18 · 12/24 · 20/60 · 30/70 |
The 2A supply configuration accepts single phase 120 or 240 V, or three phase 120–240 V. The 4D configuration takes three phase 400 or 480 V with a separate 24 VDC control supply. Interface options run from analogue voltage with pulse train, USB and RS232, through CANopen, EtherCAT and PROFINET, to a PWM power block. Frame sizes range from 150 × 43.2 mm up to 233.8 × 117.4 mm, which matters when the cabinet layout is already fixed.

Image 2. Servotronix CDHD drive range
Wiring That Decides How Commissioning Goes
Most first-power-up problems on a linear motor axis are wiring, and the same few items account for most of them.
Separation. Keep encoder and Hall cabling at least 300 mm away from the motor power conductors and the drive’s mains input. A linear motor’s power cable carries fast-switching current right alongside the moving carriage, and the feedback signal it corrupts is the one thing holding the loop together.
Cable length limits. The Adtech documentation sets 15 m between drive and motor, and 10 m for the Hall cable on EN2 at a conductor size of 0.18 mm² or larger. These are limits, not targets.
Shielding. Feedback cable shields land on the connector’s metal shell, not on a signal pin, at both the drive and the sensor end as specified.
The 5 V supply is not a general-purpose rail. The 5 V on Adtech’s EN2 is provided for the Hall elements and nothing else. On Panasonic’s X5, the external sensor supply is customer-provided and has to stay within 250 mA. Check that budget against your scale — a FAGOR EXA reading head draws 250 mA unloaded, which leaves no margin at all, so confirm the arrangement before the panel is built rather than after.
Never back-feed the sensor supply pins. Applying external voltage to EX5V and EX0V, or their equivalents, damages the drive.
Reading the Fault Codes
Fault codes on a linear motor axis point at a small number of causes, and knowing which family a code belongs to saves most of the diagnosis time.
Feedback path. Adtech’s A/B/Z line-break codes and Panasonic’s alarm 55 group both mean the drive stopped receiving what it expected from the scale. Check the connector shells, the shield termination and the routing separation before suspecting the head.
Commutation. Adtech flags an unconnected Hall input, an incorrect Hall signal and a motor phase-sequence test failure as separate codes. Panasonic’s alarm 61 group covers pole position estimation failing outright, and its listed causes are worth reading as a checklist: estimation not completed, feedback scale direction reversed, insufficient travel or time allowed for the routine, mechanical binding, and load offset or friction. A reversed scale direction is the one that most often looks like a motor fault when it is a configuration error.
Thermal. Adtech reports motor PTC over-temperature and I²t overload separately from IPM over-temperature. The first two are telling you the duty cycle is beyond the motor’s continuous rating; the third is about the drive and its cabinet.
Motion limits. Over-speed, position error exceeded and motor stall generally mean the profile is asking for something the axis cannot deliver, or that something is mechanically obstructing it.
What the Order Commits You To
Some of these can be changed later by editing a parameter. The rest cannot be changed without buying different hardware, and it is worth separating them before the purchase order goes out.
Fixed at ordering:
– Encoder format on the Adtech series — the T01 or T02 field
– Whether the drive has a Hall input at all — the P, H or C version field
– Supply voltage and phase configuration
– Continuous and peak current capability
– Fieldbus or interface type
– Frame size, against the cabinet space you have
Adjustable afterwards:
– Feedback type selection and resolution within what the hardware supports
– Pole position detection method, where more than one is available
– Gains, filters and current limits
– Communication addressing and baud rate
Send us the motor model, the scale you intend to use, the motion profile, the supply available and the controller interface, and we will specify a matched motor, scale and drive rather than three components that each meet their own specification.
Contact TechMan Robotics for linear motor drive selection.
FAQ about Linear Motor Drive
Can a standard rotary servo drive run a linear motor?
Only if it explicitly supports linear motor operation. It needs a commutation method that does not assume a fixed encoder-to-magnet relationship, an input for a scale that is not mounted on the motor, and current limits set in force rather than torque terms. Drives without these will either refuse to enable or commutate incorrectly.
Why does the axis move by itself at power-up?
That is almost always pole finding. With an incremental scale and no Hall signals, the drive has to establish where the forcer sits relative to the magnets before it can commutate, and the only way to do that is to apply current and observe. Hall signals or an absolute scale remove the movement.
The pole estimation routine fails on my vertical axis. What now?
It is not suited to that application. Panasonic’s documentation excludes vertical axes with load offset or high friction from pole position estimation, because gravity acts on the mover throughout the routine. Specify Hall feedback or an absolute scale, and treat this as a design decision rather than something to tune around.
My scale resolves finer than the drive can count. What happens?
The drive’s input rate caps the axis speed. At 4 Mpulse/s and 0.1 μm resolution the ceiling is 0.4 m/s regardless of what the motor and scale can do. Either accept the speed, drop to a coarser resolution, or move to a serial or analogue feedback route that does not push the same pulse rate.
Do I need Hall sensors on the motor?
Not always. They are one of three commutation routes, and an absolute scale or a working estimation routine replaces them. They earn their place on vertical axes, on axes with restricted travel, and where a startup movement is unacceptable. Note that on the Adtech range the Hall input exists only on the H-version drives, so this decision reaches into the drive part number.
Can several drives share one communication line?
Yes, over RS485 in MODBUS multi-drop, with 120 Ω termination at the first and last drive on the line. One limitation to plan around: the RS485 port cannot be used simultaneously with the drive tuning software, which needs RS232.
Which Linear Motor Drive brand should I choose?
It usually follows from the controller you already have and the fieldbus the machine is built on rather than from the drive itself. Tell us the controller and the feedback you intend to use and we will say which of the three platforms fits without adding interface hardware.